Ductwork from the plan to the fabrication shop: runs drawn in plan and built in 3D with their fittings, sized for their air flows, checked for pressure, noise, leakage and fire, and unrolled into flat patterns for nesting and cutting.
A 36 x 18 m office floor ventilated by one air handling unit with supply, extract, fresh-air and exhaust ductwork and a separate WC extract fan, drawn, sized, checked, costed and commissioned in Stratal CAD with HVAC Ductwork 0.7.0. The plugin wrote the schedules, pressure and fan duties, design and condensation checks, cost estimate, commissioning sheet, flat patterns and supports shown on eight A1 sheets.
Made on 12 November 2026 with Stratal CAD 0.1.8 and HVAC Ductwork 0.7.0; later versions have changes since.
The job and its names are fictional. Pictures are resized only, not retouched; the figures are the software's own output.
The model in 3D
The picture above is a render made in Stratal CAD: The whole floor from the south-east: supply (blue), extract (yellow), fresh air (green) and exhaust (brown), each with its DUCTLOOK system look (see the render larger). The live model is the job's own glTF file (2.2 MB, 65,332 triangles),
fetched only when you press the button and drawn in your browser with simple shading, so its colours and lighting are plainer than the render.
Click or tap the model to take control (the page scrolls past it until you do), then drag to turn it, right-drag or Shift-drag to move it,
and use the wheel or a pinch to zoom; press Escape or click outside to let go.
The job in numbers
Ductwork drawn
60 runs, 51 terminals, 2 units
Sheet metal (DUCTSCHED)
362.734 m2, 2293.83 kg
Duct length
196.544 m
Supply air
2400 l/s to 30 ceiling diffusers and 5 slot diffusers
Supply index run (DUCTPRESS)
192.88 Pa: SA-01 > SA-10 > SA-27 > SA-28 > SA-29
AHU-01 supply fan (DUCTFAN)
2400.0 l/s at 597.2 Pa, SFP 1.00
AHU-01 extract fan (DUCTFAN)
2250.0 l/s at 540.7 Pa, SFP 0.90
Allowed leakage, class B at 400 Pa (DUCTLEAK)
162.36 l/s
Accessories on the runs
57 (dampers, attenuators, flexible connections, test points, access doors)
Supports (DUCTHANGER)
113 hangers, 3 riser clamps, 4 floor stands
Flat patterns (DUCTFLAT)
43 parts, 71 blanks, 43 DXF files
Design check (DUCTCHECK)
6 warnings on the first pass, 0 after the fixes
Commissioning (DUCTCOMM, example readings)
2 out of tolerance at the first reading; 51 of 51 terminals Pass (second reading)
A presentation look per system, kept when runs are rebuilt (DUCTLOOK)
Face size at DUCTTERM; runs join at one level only
AHU outside-air spigots, terminal dampers, side spigots on plenum boxes
Damper Move and Remove; partial sizing; tags along each tree; numbered clash marks and CSV
Fan duties with the unit's own internal drop and fan selection from your library
Noise, leakage, heat, throws, balancing, fire dampers and supports
Sizing by equal friction or velocity, pressure drops and the index run
Schedules, flat patterns with named DXF files and a nesting job
What it does
New in 0.9.0
Added on 21 November 2026, with Stratal CAD 0.2.5.
DUCTJOINTS lists straight sections, fittings and flanged, slip or push-fit joints, with metres of joint for flange, gasket and sealant and the flange corners (CSV).
DUCTACCESS lists or places access doors for cleaning and inspection beside dampers and attenuators and at the spacing you type; the default distances are starting values, so type your specification's.
DUCTROOM totals each room's supply and extract from the terminals inside its outline, with air change rates, net flow and pressure regime; no regulation rates are bundled, you type the least rate.
DUCTCOMM can order the commissioning sheet for proportional balancing, index branch first.
Draw runs in plan, get them in 3D
Fittings follow from the geometry.
DUCTRUN: rectangular, circular and flat-oval runs by their points, with levels, rises and drops
Bends, offsets, transitions, reducers, tees and end caps worked out from the run, in plan and as solids
DUCTTERM: diffusers, slot diffusers, grilles, disc valves and louvres, with plenum boxes
DUCTEQUIP: air handling units with outside-air spigots, fans, fan coils, boxes, MVHR units and radial ducting
DUCTDAMPER: dampers and access doors on a run, moved or removed later
Size it
From the terminals' flows to the fan.
DUCTSIZE: by velocity or equal friction, from given flows or flows summed down the network
DUCTPRESS: friction, fittings and terminals per run, and the index run item by item
DUCTCOEF: your own loss coefficient library, kept in the drawing
DUCTFAN and DUCTFANSEL: fan duties and specific fan power, and the fan for each duty from your manufacturers' curves
DUCTBALANCE: what each far end's damper must absorb, and which need one
Check it
The building services checks in one place.
DUCTNOISE: duct-borne fan noise at each terminal and in the room, by octave and in dB(A)
DUCTLEAK: allowed air leakage per system at a test pressure
DUCTHEAT: air temperatures along the supply runs through their insulation
DUCTTHROW: neck velocities and throws, and jets that meet
DUCTFIRE: runs crossing fire-compartment lines, with fire or fire and smoke dampers placed and scheduled
DUCTCLASH: duct envelopes against the structure, services and each other, with numbered marks
For the fabricator
Areas, weights, patterns and supports.
DUCTSCHED: duct and fitting schedules with sheet areas and weights, terminals and units
DUCTFLAT: flat patterns of bends, transitions and reducers, a DXF file per pattern and a nesting job for True-Shape Nesting
DUCTHANGER: hangers and riser clamps with rod sizes and lengths to the soffit
Edit in one place
Many runs at once.
DUCTPROPS: every property of the selected runs, terminals and units, in the dock and at the command line
DUCTTAG: runs tagged by system and terminals by type, along each tree
DUCTUPDATE: every run, terminal and unit drawn again from its data and connections
DUCTLOOK: a render look per system, kept when runs are rebuilt
Key commands
DUCTRUN
A duct run by its points; its fittings follow from the geometry
DUCTTERM
Air terminals (diffusers, grilles, valves, louvres) with optional plenum boxes
DUCTEQUIP
An air handling unit, fan, fan coil or box with its spigots
DUCTDAMPER
A damper or access door on a run; move or remove one already there
DUCTSIZE
Size runs by velocity or equal friction
DUCTPRESS
Pressure drop per run and along the index run
DUCTFAN
Fan duties of each unit, with specific fan power against a limit
DUCTFANSEL
Your fan library and the fan for each unit's duty
DUCTBALANCE
What each far end's damper must absorb against the index path
DUCTNOISE
Duct-borne fan noise at each terminal and in the room
DUCTLEAK
Allowed duct air leakage per system at a test pressure
DUCTFIRE
Runs crossing fire-compartment lines; places fire dampers and lists them
DUCTCLASH
Duct envelopes against the drawing's solids and each other
DUCTHANGER
Hangers and riser clamps along the runs with rod sizes and lengths
DUCTSCHED
Duct and fitting schedules with sheet areas and weights
DUCTFLAT
Flat patterns of the fittings, with DXF files and a nesting job
DUCTAPPLY
Writes the properties typed in the Ductwork properties dock, as one undo step
DUCTCHECK
Every run, terminal and unit against your design limits: unbuildable runs, no flow, velocity, gradient, aspect, capped ends, unfed terminals; marks; CSV
DUCTSCHEM
Each unit's systems as a single-line schematic beside the plan: mains, branches, dampers, attenuators, terminals with flows and sizes; run again to update
DUCTSECT
A section of the ductwork on a line picked in plan by the kernel's cut, with insulation, levels, the soffit and labels; kept and drawn again (Update)
DUCTJOINTS
The joint and section list: straight sections, fittings, flanged, slip or push-fit joints, metres of joint for flange, gasket and sealant, flange corners; CSV
DUCTACCESS
Access doors for cleaning and inspection beside dampers and attenuators and at the spacing typed: Check lists them, Insert places them
DUCTROOM
Each room's supply and extract from the terminals inside its outline: air change rates, net flow and pressure regime; marks; CSV
DUCTSURR
Named areas with their own temperature and humidity (a plant room, a ceiling void) for DUCTDEW: by a plan boundary or a run's Surroundings property
Specifications
Version
0.9.0 (the job above was made with 0.7.0 and Stratal CAD 0.1.8; later versions have changes since)
Shapes
Rectangular, circular and flat-oval; circular sizes from the R20 series, rectangular sides 100 to 2000 mm
Engineering
Colebrook-White friction, loss coefficients per fitting, velocity or equal-friction sizing, index run, balancing
Checks
Fan duty and SFP, fan selection, noise by octave and dB(A), leakage, air temperatures, throws, fire dampers, clashes
Output files
CSV schedules and reports, DXF R12 flat patterns, a nesting job for True-Shape Nesting
Data
Stratal's own sizes, gauges and conservative loss coefficients; your own coefficients and fan curves imported as JSON or CSV
Requires
Stratal CAD 0.1.7 or later on Windows 11 (x64), with a licence that includes HVAC Ductwork; DUCTLOOK needs 0.1.8 or later
Delivery
A Stratal-signed plugin, installed from the Plugins menu; runs in Stratal CAD or isolated in its own process
Limitations
Loss coefficients, noise attenuation, throw constants, gauges and hanger spacings are Stratal's own conservative defaults, not DW/144, CIBSE or ASHRAE tables: check them against the project's design guide.
No manufacturer's data ships with it: terminal figures start from illustrative defaults and fan curves come from your own library.
Clashes are found against other solids' bounding boxes: a place to look, not a measured interference; terminals and units are not checked.
Transitions show in 3D as a step at their middle, and insulation has no 3D solid.
Weights are sheet only: no seams, flanges, stiffeners, hangers or sealant.
No flat pattern for flat-oval bends or for branches on round mains; the DXF files have not yet been read by a fabricator's software.
Noise leaves out regenerated noise, breakout and attenuators' insertion loss, and there are no NR curves.
DUCTLOOK needs Stratal CAD 0.1.8 or later.
DUCTFAN leaves the air handling unit's intake and exhaust paths out of the fan pressures: add them yourself (DUCTPRESS gives them).
DUCTDEW and DUCTHEAT take one temperature for all extract, return and fresh-air runs and treat exhaust runs at the supply temperature, with one set of surroundings for every run; DUCTCOST has no labour, supports or testing items.
DUCTPROPS Level on a run with a riser moves the whole run, and a run can start on another system's spigot, both with no warning: check levels and connections after such edits.
The plugin draws no system schematic, sections or elevations of the ductwork; DUCTCOMM lists weather louvres among the terminals to measure.
The office in the pictures, its structure and the sprinkler main by others are fictional and modelled with Stratal CAD's standard tools; the fan library and the cost rates are made-up examples, not a manufacturer's or a contractor's data. The pressure, noise, throw and leakage figures use Stratal's own defaults: check them against your design guide and the manufacturers' figures.
Add it to Stratal CAD
HVAC Ductwork runs inside Stratal CAD and stays with your licence.